Watts to amps calculator

Calculate electrical current from power and voltage for DC, single-phase AC or balanced three-phase AC.

Calculated in your browser.

Embed this tool

Choose what visitors see when the widget first loads.

Choose what visitors see when the widget first loads.

Values placed in published code can be read by anyone. Keep private tokens and files out of the embed.

Preview widget ↗

02 / Guide

Watts to amps calculator — How it works

Watts to amps 120V: why voltage matters

Watts describe real electrical power, whereas amperes describe current. A current cannot be calculated from watts without knowing the voltage and the kind of circuit. Enter the power in watts and the voltage that actually applies to the load. In a direct-current circuit the relation is P = V × I, so current is watts divided by volts. For example, a 1200 W DC load supplied at 120 V draws 10 A in this simplified steady-state calculation. A device rated at the same 1200 W but supplied at a different voltage draws a different current. The tool does not infer voltage from your country or from an appliance name.

Single-phase AC and power factor

For a single-phase alternating-current load, use real power P = V × I × power factor. If a 1200 W load operates at 120 V with a power factor of 0.8, its current is 1200 ÷ (120 × 0.8) = 12.5 A, not 10 A. Power factor is a ratio between zero and one and must reflect the equipment and operating condition. A purely resistive idealized load may be close to one, while motors and electronic supplies can differ. Do not confuse real power in watts with apparent power in volt-amperes; substituting a VA label into the watts field changes the meaning of the formula. A missing power factor should not be silently guessed for a real installation.

Balanced three-phase calculation

For a balanced three-phase AC load, the calculator uses P = √3 × V × I × power factor. The voltage field must contain line-to-line RMS voltage, not the phase-to-neutral value. A 6000 W balanced load on a 400 V line-to-line system with power factor 0.8 gives about 10.83 A of line current. This formula assumes the three phases share the load equally. It is not suitable for a single phase carrying most of the current, a strongly unbalanced system or an installation with unknown voltage conventions. Check the equipment plate and wiring diagram before choosing the three-phase option. The square-root-of-three factor is not used for DC or single-phase circuits.

Reading the result responsibly

The displayed amperes estimate operating current from the values you entered. It does not calculate inrush current when a motor starts, protective-device settings, conductor size, voltage drop or safe capacity of a socket. Actual power and power factor can change as equipment cycles or its load varies. Use measured values when comparing a device to a specification, and consult a qualified professional and applicable electrical rules for installation decisions. If the result looks implausible, first check whether the source lists W, kW or VA, whether the voltage is line-to-line for three-phase, and whether the power factor was entered as 0.8 rather than 80. This browser calculation sends no entered values to a server.

Watts to amps calculator — How it works
  1. Watts to amps 120V: why voltage matters
  2. Single-phase AC and power factor
  3. Balanced three-phase calculation